Eye wash station installation in Concord & the Bay Area.
OSHA-required. ANSI-compliant. Installed and documented.
OSHA requires eye wash stations anywhere hazardous materials are handled. We install plumbed emergency eyewash and combination shower/eyewash units per ANSI Z358.1 — with the documentation your safety officer needs.
- ANSI Z358.1 compliant installs — Travel distance, tepid water, and flow rate — all verified.
- OSHA compliance documentation — Installation records ready for your safety file and inspections.
- Thermostatic mixing valve installs — Tepid water (60–100°F) compliance when your supply falls outside range.
- CA Lic. #802256 — Licensed, insured, and family-owned since 2001.

ANSI Z358.1 Compliant
OSHA-required installations
What We Do
Plumbed, compliant,
and documented.
OSHA 29 CFR 1910.151(c) requires emergency eyewash access wherever employees may contact corrosive or injurious materials. That means proper unit selection, placement within 10 seconds of the hazard, tepid water delivery, and minimum 15-minute flow — all per ANSI Z358.1.
We handle the full installation: site assessment to confirm placement and water supply, unit selection, permit (if required), plumbed connection with thermostatic mixing valve when needed, flow test, and written documentation for your safety officer and OSHA compliance file.
Request a site assessmentHow It Works
Site visit to
compliance file — done.
- Step 1:
Site Assessment
We identify hazardous material locations, travel distance requirements (10 seconds / 55 feet per ANSI), and plumbing access points.
- Step 2:
Select the Right Unit
Plumbed eyewash, combination eyewash/shower, or self-contained. We recommend based on your facility layout and OSHA requirements.
- Step 3:
Install & Connect
Proper supply line connection, tepid water temperature compliance (60–100°F), and drain connection. Permit pulled if required.
- Step 4:
Test & Document
Full flow test, temperature verification, and installation documentation for your safety records and OSHA compliance file.

Installation Guide
Plumbed or self-contained — and where exactly does it need to go?
Eye wash station compliance isn't just about having a unit on the wall. Placement, water temperature, and unit type all have to meet ANSI Z358.1 to satisfy OSHA. Here's what we verify on every install.
ANSI Z358.1 key requirements
Must be reachable within 10 seconds (approx. 55 feet) from the hazard. We map your facility to confirm placement.
Must deliver tepid water (60–100°F) for 15 minutes. We verify your supply temperature and add a thermostatic mixing valve if needed.
Plumbed units require a water connection but provide unlimited flush time. Self-contained units are portable but require regular refilling and testing.
You likely need an eye wash station if you have a…
- Industrial or manufacturing facility
- Auto repair or body shop
- Restaurant with chemical cleaning agents
- Laboratory or medical facility
- OSHA inspection upcoming
- Adding or renovating a hazardous work area
FAQ
Common questions
Yes. OSHA 29 CFR 1910.151(c) requires that suitable facilities for quick drenching or flushing of the eyes and body be provided wherever employees may be exposed to injurious corrosive materials. The specific design and placement requirements are governed by ANSI Z358.1.
ANSI Z358.1 is the American National Standard for Emergency Eyewash and Shower Equipment. It defines requirements for flow rate, water temperature (tepid, 60–100°F), activation, placement (within 10 seconds / approximately 55 feet from the hazard), and minimum flush duration (15 minutes). Compliance with ANSI Z358.1 is the accepted way to satisfy OSHA's eyewash facility requirement.
Cost depends on unit type (plumbed eyewash vs. combination shower/eyewash), proximity to existing water and drain lines, whether a thermostatic mixing valve is needed for tepid water compliance, and permit requirements. We assess your facility and provide a clear quote before any work begins. Call us for a facility walkthrough.
Plumbed units connect directly to your water supply and provide continuous flow for 15+ minutes without refilling — they are the preferred solution wherever a water line is accessible. Self-contained units are portable and require no plumbing connection, but must be refilled and inspected weekly per ANSI Z358.1. We can install either type and will recommend based on your facility layout and hazard locations.
Tepid water is defined by ANSI Z358.1 as water delivered between 60°F and 100°F. Water that is too cold can cause shock or hypothermia; water that is too hot can accelerate chemical injury. If your facility's cold water supply runs below 60°F or your hot water supply exceeds 100°F at the outlet, a thermostatic mixing valve is required. We test your supply temperature during the site assessment and install a mixing valve if needed.
We provide written installation documentation suitable for your OSHA compliance file and safety records. This includes the unit type and model, location, supply line and drain connection details, flow test results, and temperature verification. Your safety officer will have what they need for any OSHA inspection.
Yes. ANSI Z358.1 requires that plumbed eyewash stations be activated weekly (typically by facility staff) and inspected annually. We offer annual inspection visits to verify flow rates, check water temperature, inspect components for wear, and update your compliance documentation. Ask about a service agreement if you have multiple stations.
What Clients Say
Trusted by safety managers
and facility operators.
“Our safety manager needed eye wash stations installed at two locations before an OSHA walk-through. Guerra Bros. assessed both sites, installed plumbed units, and handed us the documentation the same week. Inspection went smoothly.”
“We had no idea we needed a thermostatic mixing valve until they tested our cold water supply. They caught it during the site visit, installed everything correctly, and gave us a full compliance packet for our records.”
“Running a manufacturing facility means OSHA compliance is non-negotiable. Guerra Bros. mapped our entire floor for travel distance requirements and installed four stations in one day. Professional from start to finish.”
Where We Work
Eye Wash Station Installation near you.
Same-day service available in Concord, Walnut Creek, Martinez, and throughout Contra Costa County.
Don't see your city? Call us — we may still serve your area.
View all service areasRelated Services
More commercial services
For Commercial
Tenant Improvements
Full plumbing buildouts for commercial tenant improvements — from rough-in to final inspection.
View Service
Full facility buildouts
For Commercial
Gas Line Services
Commercial gas line installation, repair, and pressure testing for industrial and commercial facilities.
View Service
Industrial gas work
For Commercial
Backflow Testing & Repair
Certified backflow preventer testing, repair, and compliance report filing for commercial properties.
View Service
Annual compliance